CFM Corporation Indoor Fireplace UVDR36C User Manual

Ventless Fireplace  
Models: UVDR36C  
UVDR42C  
INSTALLER/CONSUMER  
SAFETY INFORMATION  
Read and save  
these instructions.  
This book contains your installation instruc-  
tions and should be kept in a safe place. For  
you to realize all the advantages and use of  
the reliable service that has been engineered  
into your CFM Corporation fireplace, you  
must carefully follow all of the instructions  
contained in this book regarding installation  
and operation of the fireplace.  
These instructions should be read carefully  
in their entirety before beginning installation  
of the fireplace.  
It is suggested that you wear work gloves  
and safety glasses to protect your hands and  
eyes when installing your fireplace. NOTE:  
Authorities having jurisdiction (i.e. building  
inspectors, fire marshals, etc.) should be  
consulted before installation to determine the  
need to obtain a permit.  
Homeowner’s Installation and  
Operating Manual  
When installing the Blower Kit, it is neces-  
sary to bring the power source to the fire-  
place before walls are enclosed. Refer to  
Blower Kit instructions.  
These fireboxes are approved as univer-  
sal fireboxes and can be paired with any  
ANSI Z21.11.2 approved vent-free log set.  
The vent-free log manufacturer’s instruc-  
tions - including their required dimen-  
sional clearances for firebox size, - must  
be followed.  
Refer to the manual that is packed with the  
log set for operating instructions.  
INSTALLER: Leave this manual with the appliance.  
CONSUMER: Retain this manual for future reference.  
Not for use in bedroom or bathroom installa-  
tions.  
20007469 9/07 Rev. 5  
 
UVDR Series Unvented Gas Fireplaces  
Fireplace Dimensions  
P
Rough  
Opening  
Depth  
K
L
H
N
P
1/2” Clearance to  
Rough Opening Width C  
M
Combustibles not Required  
at this Point  
Rough  
Opening  
Height  
F
1/2” Clear-  
ance to  
Combustibles  
not Required  
at this Point  
E
E
B
D
A
J
6"  
Gas Line  
Access  
C
G
Fig. 1a UVDR36/42C specifications and framing dimensions.  
UVDR36C  
UVDR42C  
42”  
A
B
C
D
E
F
G
H
J
36”  
21⁷⁄₈”  
39”  
21⁷⁄₈”  
45”  
7”  
35”  
38¹⁄₄”  
9”  
21”  
8⁵⁄₈”  
22”  
21”  
8”  
39”  
42¹⁄₄”  
10¹⁄₂”  
22”  
9³⁄₄”  
32”  
22”  
K
L
M
N
P
65”  
32¹⁄₂”  
46”  
76¹⁄₄”  
38¹⁄₈”  
54”  
20007469  
3
 
UVDR Series Unvented Gas Fireplaces  
Installation Instructions  
If the fireplace is to be installed on a raised wooden  
platform, the platform must be a continuous level sur-  
face. The fireplace must be secured in place so it can-  
not shift positions. The nailing flanges on the sides of  
the firebox make securing it to the framing easy. They  
were designed to allow the installation of 1/2” wallboard  
or plywood flush with the face of the fireplace.  
Locating the Fireplace  
Figure 2 shows some of the many ways your fireplace  
may be installed. Consider the traffic pattern in your  
room and the location of doors and windows. Moving  
air from ceiling fans, open doors and hot air grilles may  
cause the flames to soot. If a disturbance is found that  
effects the flames, it must be eliminated by turning off  
the ceiling fan, closing the door or closing or moving  
the hot air register. A corner location may be best where  
space is limited.  
Only the header (Fig. 1) may rest on the standoffs on  
top of the firebox.  
When the fireplace is installed over carpeting, vinyl, tile  
or any combustible material other than wood flooring, it  
must be installed on a metal or wood panel extending  
its full width and depth. Alternatively, the carpeting, vinyl  
tile, etc., may be removed from beneath the fireplace  
before installing. COMBUSTIBLE MATERIALS MUST  
NOT BE INSTALLED OVER OR TOUCH ANY BLACK  
PAINTED SURFACE. DO NOT BLOCK HEAT CIRCU-  
LATING AIR OUTLETS. DOING SO MAY RESULT IN  
POTENTIAL FIRE HAZARD.  
Your fireplace weighs no more than some of your fine  
furniture. If the fireplace is located near a load bear-  
ing wall, additional supports to the foundation will not  
be necessary. HEAVY FACINGS SUCH AS BRICK,  
STONE, ETC., MAY REQUIRE ADDITIONAL FOUNDA-  
TION SUPPORT.  
ALTHOUGH THIS UNIT MAY BE INSTALLED ON  
COMBUSTIBLE SURFACES, IT MUST NOT BE IN-  
STALLED ON CARPET OR VINYL.  
Clearances  
To ensure a safe installation the following instructions  
must be carefully observed.  
Room Divider  
1. Sidewall Clearances: Clearances from the side of  
the fireplace opening to any combustible wall should  
not be less than 5”. (Fig. 3a)  
Partial Room  
Projection  
2. Ceiling Clearances: The ceiling height should not  
be less than 42” from the top of the fireplace open-  
ing.  
Full Room  
Projection  
Corner  
3. Mantel Clearances:  
a. If the fireplace has no mantelpiece, then the heat  
resistant material must extend upwards a dis-  
tance of at least 9¹⁄₂" from the fireplace opening.  
A mantel projection must be a minimum of 24”  
above the top fireplace opening if a canopy is not  
installed. (Fig. 3b)  
Flush  
T224  
Fig. 2 Locating the fireplace.  
b. Noncombustible materials used in this installation  
such as slate, marble, tile, etc. must be at least  
1/2" thick. Do not install a combustible material  
behind sheet metal. Failure to use noncombus-  
tible materials above the opening as specified  
in these instructions may cause damage to the  
materials used and create a fire hazard.  
c. A heat reducing canopy is shipped with the  
fireplace. Use of this canopy is optional in order  
to reduce mantel heights as shown in Figure 3d.  
If the canopy is installed, a combustible mantel  
piece may project 2" from the wall at 6¹⁄₂" above  
the fireplace opening. A 6" mantel projection at  
13" above the fireplace opening and a 10" projec-  
tion at 22" above the opening. (Fig. 3a and 3d)  
To install the optional canopy, remove the four (4)  
screws supplied with a Phillips screwdriver. Two (2)  
Gas Line  
The gas line must be installed before framing in the fire-  
place by a licensed gas line installer.  
Drafts  
Do not locate the fireplace in high traffic areas or areas  
exposed to high drafts and winds. Locate the fireplace  
away from furniture and draperies.  
Fireplace Clearances  
The fireplace may be placed directly on a combustible  
floor, against a combustible wall at marked clearances  
or on a raised wooden platform.  
4
20007469  
 
UVDR Series Unvented Gas Fireplaces  
Clearance to Combustible  
Mantel Projections with 4”  
Clearance to Combustible  
Mantel Projections without  
Canopy  
3a  
3c  
3d  
Canopy  
42"  
24  
22  
20  
18  
16  
14  
12  
10  
8
22  
20  
18  
16  
14  
12  
10  
5" Min.  
Combustible Per-  
pendicular Wall  
3b  
10"  
Clearances  
without Canopy  
8
6
6"  
24"  
Min.  
2
4
6
8
10  
2
4
6
8
10  
Noncombustible  
Material  
Mantel (Combustible)  
Projections (“)  
16"  
Min.  
*Combustible Projections  
above the fireplace must be  
within the area described by the  
dashed line.  
9"  
Min.  
Fireplace  
Opening  
FP604b  
T225  
Fig. 3 Clearances to combustibles.  
Step 1: Framing the Firebox  
screws are located across the top of the fireplace  
opening approximately 5” to the right and left from  
center. Two (2) screws are located 4” down from  
the top on each side of the fireplace opening. Place  
the canopy, making sure the 1/4” hex head screws  
across the top of the opening align with the clear-  
ance holes in the canopy. Secure with the four (4)  
previously removed screws.  
The width of the framed opening must be 39” for 36”  
models or 45¹⁄₄" for 42" models. (Fig. 4)  
The entire fireplace can be elevated above the floor  
to achieve a raised hearth effect. This can be done by  
adding a small platform to achieve the desired height.  
NOTE: Refer to Pre-wiring the Junction Box and Electri-  
cal Service on Page 7.  
WARNING: The firebox canopy must not be modified  
or replaced with a canopy that may be provided with  
the unvented decorative room heater.  
Step 2: Install the Firebox  
Install the firebox into the framed opening by setting  
it directly in front of the opening and sliding it into the  
proper position.  
4. Floor Clearances: No clearance is required if the  
appliance is installed per these instructions.  
Step 3: Level the Firebox  
Installing the Firebox  
Check the level of the firebox on the top edge of the fire-  
place face. Shim if necessary.  
This list of specific instructions will help you make cer-  
tain that every installation operation is done correctly.  
Complete the installation steps in the sequence shown.  
Step 4: Secure the Firebox  
Four (4) nailing flanges are supplied with the fireplace  
(found on the fireplace hearth). To level the box and  
secure it firmly in place, remove the nailing flanges from  
the hearth and install at the sides of the fireplace as  
shown in Figure 5.  
LOCAL BUILDING CODES SHOULD BE CONSULTED  
IN ALL CASES AS TO THE PARTICULAR REQUIRE-  
MENTS CONCERNING THE INSTALLATION OF FAC-  
TORY BUILT FIREPLACES.  
Select the location for the fireplace by taking into con-  
sideration the factors previously outlined in the Locating  
the Fireplace section of the manual.  
NOTE: The nailing flanges have two (2) sets of holes  
to allow for adjustment for 1/2” or 5/8” offset of the face  
of the unit. When installing the nailing flanges, choose  
the set of holes on the nailing flange that fit with your  
application.  
20007469  
5
 
UVDR Series Unvented Gas Fireplaces  
The normal gas connection is 1/2” NPT, made at the left  
side facing the unit. If a right side connection is desired,  
the connecting pipe must be led at the rear of the fire-  
place to terminate at the left hand side for connection to  
the fireplace.  
D
1/2"  
C
Noncombustible Insulation  
5"  
A
1/2” Clearance  
not Required at  
This Point  
Side Refractory  
1"  
Min.  
Refractory  
Cement  
Fireplace  
Outer Wrap  
1/2” Gas Pipe  
T227  
Fig. 6 Gas line installation.  
Piping should be tested for leaks prior to final wall  
installation. Test for leaks using soap and water solution  
after completing the connection. DO NOT USE OPEN  
FLAME.  
Step 6: Optional Procedure For Cold Climate Instal-  
lations  
B
B
The insulation and sealing of the enclosure around the  
fireplace is very important in cold climates. If the en-  
closure is insulated and sealed properly, you can avoid  
future cold air problems. The time taken to install the  
firebox correctly is well worthwhile. The following steps  
are to stop potential cold air problems.  
A
Side View  
Front View  
T226  
Insulation of the Fireplace Enclosure  
A
39”  
45”  
B
38¹⁄₄”  
42¹⁄₄”  
C
21”  
22”  
D
22’  
32”  
When in a chase or an outside wall, the fireplace en-  
closure should be insulated like any other wall of your  
home. Insulation should be installed on the outside  
wall(s) and the wall above the fireplace.  
36” Models  
42” Models  
Fig. 4 Framing dimensions.  
Insulate to Seal Under the Fireplace  
Insulating under the fireplace is beneficial for installa-  
tions on a concrete slab. The fireplace should be placed  
on insulating board. It is important that a hard, rigid  
surface be maintained, so do not use fiberglass insula-  
tion for this purpose.  
CAUTION: WHEN INSTALLING A FIREPLACE IN AN  
INSULATED ENCLOSURE, BE SURE TO MAINTAIN  
ALL MARKED AIR SPACES.  
Nailing  
Flanges  
Seal Seams  
Seal the seams of the fireplace where the outer wall  
meets the bottom pan and the front face. Also seal  
between the fireplace and finishing materials. Use high  
temperature caulk. Refer to Figure 7 for details of seal-  
ing spaces between the fireplace and finishing materi-  
als. Note the small amount of insulation installed across  
the top of the fireplace and down the sides as a backing  
for the caulk.  
FP1532  
Fig. 5 Secure firebox.  
Step 5: Gas Piping and Connection  
The gas piping must be installed in accordance with  
local codes or, in the absence of local codes, in accor-  
dance with the National Fuel Gas Code, ANSI Z223.1/  
NFPA 54, latest edition.  
6
20007469  
 
UVDR Series Unvented Gas Fireplaces  
Finishing Material  
Hearth Extension  
A hearth extension may be used but is not required for  
these fireboxes.  
Stud  
Insulation  
Noncombustible Material  
Caulking or Sealant  
A raised hearth extension may be used as shown in  
Figure 8.  
Hearth Brick  
Seal with Noncom-  
bustible Material  
Side View  
1/2"  
Hearth  
Extension  
Stand-  
off  
Noncombustible  
Insulation  
Finishing Material  
Combustibles Al-  
Surround  
lowed  
Top View  
Caulking or Sealant  
(no carpet or vinyl)  
FP568  
Combustible  
Plateform  
Fig. 7 Sealing spaces between fireplace and finishing materi-  
als.  
T238  
Finishing the Fireplace  
Fig. 8 A raised hearth extension.  
There are a wide variety of finishing materials avail-  
able for your fireplace from formal wall treatments with  
marble and mantels to rustic wood paneling, stone or  
brick.  
Pre-Wiring of Junction Box  
Wiring should be connected at the junction box located  
on the right side of the firebox prior to the installation of  
the blower kit. A standard wall box should be used to  
contain the SCVS - Variable Speed Control Kit.  
IT IS IMPORTANT THAT THE BLACK FACE OF THE  
FIREPLACE NOT BE COVERED WITH ANY TYPE OF  
COMBUSTIBLE MATERIAL.  
Electrical Services  
Noncombustible facing materials such as marble, brick  
or ceramic tile may overlap the black face of the fire-  
place up to the opening on either side of the fireplace.  
Seal all joints between the black fireplace face and the  
wall covering with a heat-resistant material such as rock  
wool insulation or mortar. Be sure to use high tempera-  
ture adhesive or mortar when anchoring brick, stone or  
tile to the face of the fireplace. Check to see whether  
man-made brick and stone are made of noncombustible  
materials before using them on the face of the fireplace.  
Some of these products contain combustible materials.  
Combustible wall coverings such as paneling or wall-  
board may not overlap the black face of the fireplace.  
The space between the wall covering and the fireplace  
should be sealed with a heat-resistant material such as  
rock wool insulation or mortar.  
If an electrical supply of 120V is being roughed in to the  
fireplace junction box to provide for future installation of  
optional blower kit, the wiring should be connected to  
the junction box located on the right side of the firebox.  
NOTE: All electric connections are to be made in ac-  
cordance with CSA Standard C22.1-Canadian Electrical  
Code part 1 or with the National Electrical Code, ANSI/  
NFPA 70 (latest edition) and/or in accordance with local  
codes.  
CAUTION: Should this blower require servicing, the  
power supply must be disconnected.  
M
120  
Volt  
Speed Control  
NOTE: An “L” shaped steel lintel must be installed  
across the top of the firebox opening where facing  
materials such as brick or stone are used on the face  
of the firebox. It acts as a support/firestop. It should be  
attached to the face of the fireplace with screws and  
sealed to the fireplace with a heat-resistant sealer.  
Switch  
Black  
White  
Firebox Acces-  
G
sory Junction  
Box  
Wall Electrical Box  
T229  
WARNING: The firebox screens must be in place be-  
fore operating the fireplace.  
Fig. 9 Blower wiring diagram.  
WARNING: These vent free fireplaces are not to be  
used with glass doors.  
20007469  
7
 
UVDR Series Unvented Gas Fireplaces  
Step 2: The SCVS - Variable Speed Control Kit (or  
standard wall switch) should be installed before the  
blower assembly installation. Please refer to instruc-  
tions found in the SCVS Kit.  
Blower Installation  
BEFORE YOU BEGIN...A FEW BASIC RULES  
1. Check to ensure that electrical service has been  
provided to the junction box located in the bottom  
chamber of the firebox.  
Step 3: Remove the metal hearth cover and the bot-  
tom two right brick panels from the fireplace and care-  
fully place them to the side to prevent damage.  
2. Check local building codes before installation of the  
firebox and the blower kit.  
Step 4: Locate the blower access cutout found at the  
rear of the hearth pan. Next, remove tape backing from  
tape on blower housing. Center the blower assembly in  
the access cutout area with the blower outlet duct point-  
ing upward, then press firmly to attach foam tape to the  
back and bottom of the fireplace. (Fig. 10)  
3. All wiring must be installed and/or inspected as  
necessary to comply with the local authority having  
jurisdiction.  
4. The circuit breaker controlling the power supply to  
the pre-wired junction box in the appliance must be  
in the “OFF” position before beginning installation of  
the blower.  
Step 5: Locate the junction box cutout found on the  
right side of the hearth pan. Route the powercord under  
the hearth pan and plug it into the receptacle outlet  
found in the junction box. (Fig. 11)  
5. The appliance, when installed, must be electrically  
grounded in accordance with local codes or - in the  
absence of local codes - with the National Electri-  
cal Code, ANSI/NFPA 70 or the Canadian Electrical  
Code, CSA C22.1.  
Step 6: Turn power back on and test blower operation.  
Step 7: Replace the metal hearth cover and the bottom  
two center panels in the fireplace.  
Read all the installation instructions for the appli-  
cable appliance before beginning the installation of  
the blower.  
Blower  
Access  
Cutout  
inHearth  
Pan  
Back Firebrick  
UVDR36C Blower Installation  
Step 1: Carefully unpack the blower assembly and  
familiarize yourself with the parts. Care should be taken  
not to damage the fan blades or housing.  
Step 2: The SCVS - Variable Speed Control Kit (or  
standard wall switch) should be installed before the  
blower assembly installation. Please refer to instruc-  
tions found in the SCVS Kit.  
Step 3: Remove the bottom brick from the fireplace  
and carefully place it to the side to prevent damage.  
Use a flat blade screwdriver to gently lift up the front  
edge of the brick, then pull forward to remove.  
NOTE: Hearth brick and/or hearth cover is removed as  
shown to gain access for blower and junction box instal-  
lation.  
T230  
Step 4: Locate the blower access cutout found at the  
rear of the hearth pan. Next, remove tape backing from  
tape on blower housing. Center the blower assembly in  
the access cutout area with the blower outlet duct point-  
ing upward, then press firmly to attach foam tape to the  
back and bottom of the fireplace. (Fig. 10)  
Fig. 10 Blower access.  
Receptacle  
Outlet in Juc-  
tion Box  
Step 5: Locate the junction box cutout found on the  
right side of the hearth pan. Route the powercord under  
the hearth pan and plug it into the receptacle outlet  
found in the junction box. (Fig. 11)  
Step 6: Turn power back on and test blower operation.  
Step 7: Replace the bottom brick in the fireplace.  
UVDR42C Blower Installation  
Step 1: Carefully unpack the blower assembly and  
familiarize yourself with the parts. Care should be taken  
not to damage the fan blades or housing.  
Junction Box Cutout in Hearth  
T231  
Pan of Firebox  
Fig. 11 Route powercord under the hearth pan and plug into  
the receptacle outlet.  
8
20007469  
 
UVDR Series Unvented Gas Fireplaces  
should be caulked around its perimeter to assure a  
tight seal. The rain cap opening should be positioned  
downward. (Fig. 15)  
Install Optional Outside Air Kit  
The AKU3 Outside Air Kit can be installed to bring com-  
bustion air to the heated room air. The air that is drawn  
into the heated room air from outside the home or un-  
heated area helps relieve the pressure in the home.  
The duct termination should be located so it is exposed  
to an out-of-doors opening at least 100 square inches. If  
the duct termination must be located in a crawl space or  
basement, be sure the termination area has 100 square  
inches of ventilation opening to outside air.  
The Outside Air Kit is now installed and ready for use.  
Soffit Termination  
Attic  
The duct termination must be located so it does not  
compete for air flow with exhaust fans, gas vent hoods  
or other air consuming devices or appliances. It must  
not be obstructed by rafters, insulation materials or  
other obstructions. The less restrictive the air supply,  
the better the outside air kits will perform.  
Duct  
Ceiling  
Termination  
40’ Max.  
Duct Run  
Duct  
It is good practice to protect your hands and eyes  
during installation by wearing work gloves and safety  
glasses.  
CAUTION: Do not install termination into a garage  
or other area that could contain flammable liquids  
or fumes, or into an attic space.  
Exterior Wall Termination  
Installation Instructions  
Determine the location of the fireplace as described  
in the fireplace installation manual. Then plan location  
of the duct termination and the route of the duct run  
between the fireplace and the duct termination.  
Exterior Wall  
Duct run must be limited to a maximum distance of 40’  
(12.2m) from the fireplace pipe collar to duct termina-  
tion. This will provide the least restriction to air flow. No  
more than four (4) 90° elbows can be used. Duct run  
may be horizontal, vertical, inclined or any combina-  
tion of these. (Fig. 12) You are now ready to install the  
Outside Air Kit.  
40’ Max. Duct Run  
Rain Cap  
Duct Termination  
Duct  
FP1060  
1. Remove the screws retaining the outside air cover-  
plate, if provided. (Located on the left side of front  
open units, on backside of multisided units.) Discard  
coverplate. (Fig. 13)  
Fig. 12 Typical outside air installations.  
2. Secure the inlet collar assembly to the outer casing  
with four screws (not provided). (Fig. 14)  
Cover Plate  
3. Slide the duct over the collar and attach the duct  
to the collar using the plastic tie straps or three (3)  
screws (screws not provided). Continue attaching  
the ducting together using three (3) screws at each  
joint until you have installed sufficient duct to arrive  
at your duct termination locations.  
4. At the termination end, install the duct termination.  
This should be installed from the outside of the  
home. Cut a hole in the desired location approxi-  
mately 4¹⁄₂” (114mm) in diameter, caulk around the  
hole, and slide the termination through the opening  
from outside the home. The termination/rain cap  
KT143  
Fig. 13 Remove outside air cover plate and discard, retain  
screws.  
20007469  
9
 
UVDR Series Unvented Gas Fireplaces  
Operating Precautions and Instructions  
Operation is automatic. A slight negative pressure inside  
the house will open the barometric flapper valve.  
Periodically inspect the duct termination for any block-  
age. Correct if necessary.  
KT145  
Fig. 14 Secure the inlet collar assembly.  
Duct Ter-  
mination  
Caulking  
Rain  
Cap  
Wall  
FP1061  
Fig. 15 Caulk and install duct termination/rain cap in place.  
10  
20007469  
 
UVDR Series Unvented Gas Fireplaces  
6
7
5
2
1
3
8
4
9
12  
10  
13  
11  
14  
7469  
CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time,  
without notice.  
UVDR36/42C Series Unvented Fireplaces  
Description  
UVDR36C  
68403  
66146  
62222  
68779  
73535  
73498  
75752  
--  
UVDR42C  
65864  
62197  
62222  
69554  
73395  
--  
1. Firescreen Rod (2 per fireplace)  
2. Firescreeen w/Rings (2 per fireplace)  
3. Screen Retainer (4 per fireplace)  
4. Black Canopy  
5. Back Brick  
6. Right Side Brick  
7. Left Side Brick  
8. Side Brick (2 per fireplace)  
9. Bottom Brick  
--  
73394  
--  
73500  
--  
10. Bottom Left Brick  
79013  
79014  
79015  
78988  
2253160  
11. Bottom Middle Right/Left Brick  
12. Bottom Right Brick  
13. Cover, Hearth  
--  
--  
--  
14. Nailing Flange - Bag of 4 w/Screws  
2253160  
20007469  
11  
 
UVDR Series Unvented Gas Fireplaces  
Accessories  
Decorative Surrounds  
Blower Kit  
SPB36  
SPB42  
BL-4 or FK12  
(Junction box is provided with fireplace)  
Variable Speed Control  
Heat Reducing Canopy  
SCVS  
UC36PB (UVDR36C) Polished Brass  
UC42PB (UVDR42C) Polished Brass  
BC36L (UVDR36C)  
BC42L (UVDR42C)  
AKU3  
Brick Canopy  
Outside Air Kit  
Contact CFM Corporation for questions concerning  
prices and policies covering replacement parts. Parts  
may be ordered through your Majestic Fireplaces dis-  
tributor or dealer.  
Servicing  
Repair and replacement work should only be done by a  
qualified service person.  
Always shut off the gas supply and make sure the appli-  
ance is cool before beginning any service operation.  
You will need the correct name, part number and model  
number of the appliance when ordering replacement  
parts.  
Always check for gas leaks after servicing.  
Should you need additional information beyond what  
your dealer can furnish, contact:  
CFM Corporation  
410 Admiral Blvd.  
Mississauga, Ontario  
Canada L5T 2N6  
12  
20007469  
 
UVDR Series Unvented Gas Fireplaces  
20007469  
13  
 
UVDR Series Unvented Gas Fireplaces  
14  
20007469  
 
LIMITED LIFETIME WARRANTY  
PRODUCT COVERED BY THIS WARRANTY  
All Vermont Castings gas stoves, gas inserts, and gas fireplaces, and all Majestic or Northern Flame brand gas fireplaces  
equipped with an Insta-Flame Ceramic Burner, or standard steel tube burner.  
BASIC WARRANTY  
Any part and/or component replaced under the provisions of this  
warranty is covered for six months or the remainder of the original  
warranty, whichever is longest.  
CFM Corporation (hereinafter referred to collectively as the Company)  
warrants that your new Vermont Castings or Majestic Gas Fireplace/  
Stove is free from manufacturing and material defects for a period of  
one year from the date of purchase, subject to the following conditions  
and limitations.  
This warranty is limited to the repair of or replacement of part(s) found  
to be defective in material or workmanship, provided that such part(s)  
have been subjected to normal conditions of use and service, after  
said defect is confirmed by the Company’s inspection.  
EXTENDED LIFETIME WARRANTY  
The company may, at its discretion, fully discharge all obligations  
with respect to this warranty by refunding the wholesale price of the  
defective part(s)  
The heat exchanger, where applicable, and combustion chamber  
of every Vermont Castings or Majestic gas product is warranted for  
life against through wall perforation. All appliances equipped with an  
Insta-Flame Ceramic Burner have limited lifetime coverage on the  
ceramic burner plaque. Warrantees are made to the original owner  
subject to proof of purchase and the conditions and limitations listed  
on this Warranty Document  
Any installation, labor, construction, transportation, or other related  
costs/expenses arising from defective part(s), repair, replacement,  
or otherwise of same, will not be covered by this warranty, nor shall  
the Company assume responsibility for same. Further, the Company  
will not be responsible for any incidental, indirect, or consequential  
damages except as provided by law.  
COMPONENT WARRANTY  
CAST IRON: All external and internal cast iron parts are warranted for a  
period of three years.  
SOME STATES DO NOT ALLOW FOR THE EXCLUSION OR  
LIMITATIONS OF INCIDENTALAND CONSEQUENTIAL DAMAGES  
OR LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY  
LASTS, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOUR  
CIRCUMSTANCES. THIS WARRANTY GIVES YOU SPECIFIC  
RIGHTSANDYOU MAYHAVE OTHER RIGHTS WHICH VARYFROM  
STATE TO STATE.  
Note: On porcelain enamel finished external parts and accessories  
The Company offers no Warranty on chipping of enamel surfaces.  
Inspect all product prior to accepting it for any damage to the  
enamel.  
The salt air environment of coastal areas or a high humidity  
environment can be corrosive to the porcelain enamel finish. These  
conditions can cause rusting of the cast iron beneath the porcelain  
enamel finish, which will cause the finish to flake off.  
All other warranties-expressed or implied- with respect to the product,  
its components and accessories, or any obligations/liabilities on the  
part of the Company are hereby expressly excluded.  
The Company neither assumes, nor authorizes any third party to  
assume on its behalf, any other liabilities with respect to the sale of  
this Vermont Castings or Majestic product  
Dye lot variations with replacement parts and/or accessories can  
occur and are not covered by warranty.  
GLASS DOORS: Glass doors are covered for a period of one year.  
Glass doors are not warranted for breakage due to misuse or accident.  
Glass doors are not covered for discoloration or burned in stains due to  
environmental issues, or improper cleaning and maintenance.  
The warranties as outlined within this document do not apply to  
chimney components or other non CFM Corporation accessories used  
in conjunction with the installation of this product..  
Damage to the unit while in transit is not covered by this warranty but  
is subject to claim against the common carrier. Contact the dealer  
from whom you purchased your fireplace/stove (do not operate the  
appliance as this might negate the ability to process the claim with the  
carrier).  
BRASS PLATED PARTS AND ACCESSORIES: Brass parts should be  
cleaned with Lemon oil only. Brass cleaners cannot be used. Mortar  
mix and masonry cleaners may corrode the brass finish. The Company  
will not be responsible for, nor will it warrant any brass parts which are  
damaged by external chemicals or down draft conditions.  
The Company will not be responsible for:  
GAS VALVES: Gas valves are covered for a period of one year  
a) Down drafts or spillage caused by environmental conditions such  
as near-by trees, buildings, roof tops, hills, or mountains.  
b) Inadequate ventilation or negative air pressure caused by  
mechanical systems such as furnaces, fans, clothes dryers, etc.  
ELECTRONIC AND MECHANICAL COMPONENTS: Electronic and  
mechanical components of the burner assembly are covered for one  
year. All steel tube burners are warranted for one year.  
ACCESSORIES: Unless otherwise noted all components and CFM  
Corporation company supplied accessories are covered for a period of  
one year.  
This warranty is void if:  
a) The fireplace has been operated in atmospheres contaminated by  
chlorine, fluorine, or other damaging chemicals.  
b) The fireplace has been subjected to prolonged periods of  
dampness or condensation  
c) Any damages to the fireplace, combustion chamber, heat  
exchanger or other components due to water, or weather damage,  
which is the result of but not limited to, improper chimney/venting  
installation.  
CONDITIONS AND LIMITATIONS  
This new Vermont Castings or Majestic product must be installed by  
a competent, authorized, service contractor. A licensed technician, as  
prescribed by the local jurisdiction must perform any installation/service  
work. It must be installed and operated at all times in accordance with  
the Installation and Operating instructions furnished with the product.  
Any alteration, willful abuse, accident, or misuse of the product shall  
nullify this warranty.  
d) Any alteration, willful abuse, accident, or misuse of the product  
has occurred.  
This warranty is non-transferable, and is made to the original owner,  
provided that the purchase was made through an authorized supplier  
of the Company.  
IF WARRANTY SERVICE IS NEEDED…  
1) Contact your supplier. Make sure you have your  
warranty, your sales receipt, and the model/serial  
number of your CFM Corporation product.  
2) DO NOT ATTEMPT TO DO ANY SERVICE WORK  
YOURSELF.  
The customer must pay for anyAuthorized Dealer in-home travel fees  
or service charges for in-home repair work. It is the dealers option  
whether the repair work will be done in the customer’s home or in the  
dealer’s shop.  
If upon inspection, the damage is found to be the fault of the  
manufacturer, repairs will be authorized at no charge to the customer  
parts and/or labor.  
 
CFM Corporation  
410 Admiral Blvd. • Mississauga, Ontario, Canada L5T 2N6  
 

Big Agnes Camping Equipment Royal Flush 3 User Manual
BOXLIGHT Projector MP 385T User Manual
Brocade Communications Systems Switch 53 1002580 01 User Manual
Broil King Convection Oven POV 013 User Manual
Broil King Gas Grill 9865 24 User Manual
Brother Sewing Machine PE 700 User Manual
Cambridge SoundWorks Speaker System FPS1800 User Manual
Campbell Hausfeld Paint Sprayer DH5000 User Manual
Cannon Digital Camera PS1025 User Manual
Carrier Air Conditioner 30RB060 390 User Manual